Liquid Relief Sizing & Viscosity Correction Factors (Kv)
API RP 520 Part I liquid relief sizing, viscosity correction factor (Kv), overpressure allowances (10% vs 21%), and backpressure derating (Kw).
1. Theoretical Foundations & Engineering Mechanics
Liquid Relief Valve Sizing per API RP 520 Part I
Unlike compressible gases, liquids do not expand or choke acoustically at the throat. Liquid flow through a relief valve follows the classic orifice discharge law derived from Bernoulli’s theorem.
1. Sizing Formulation
The required effective discharge area for liquid service is:
$$A = \frac{Q}{K_d K_w K_v K_c} \sqrt{\frac{SG}{P_1 - P_b}}$$
where:
- $Q$: Relieving liquid volumetric flow rate ($\text{gpm}$ or $\text{m}^3\text{/h}$)
- $K_d$: Discharge coefficient ($0.65$ for standard API liquid calculation at 10% overpressure per API 520)
- $K_w$: Balanced bellows backpressure correction factor for liquid ($1.0$ for conventional valves)
- $K_v$: Viscosity correction factor ($K_v = 1.0$ for non-viscous liquids where $Re > 100,000$)
- $K_c$: Rupture disc combination factor ($1.0$ bare, $0.90$ with rupture disc)
- $SG$: Specific gravity of liquid at relieving temperature relative to water at $15.6^\circ\text{C}$
- $P_1$: Upstream set pressure plus allowable overpressure ($P_{set} \times 1.10 + P_{atm}$)
- $P_b$: Total backpressure (superimposed + built-up)
2. Viscosity Correction ($K_v$)
For heavy fuels, lubricating oils, resins, or chilled viscous glycols, laminar boundary layer viscous dissipation reduces discharge flow capacity.
First, calculate preliminary area $A_{unviscous}$ with $K_v = 1.0$. Then compute nozzle Reynolds number:
$$Re = \frac{Q (2800 \cdot SG)}{\mu \sqrt{A}} \quad \text{or} \quad Re = \frac{Q_{m^3/h} \cdot \rho}{d \mu}$$
Then determine $K_v$:
$$K_v = \left(0.9935 + \frac{2.878}{\sqrt{Re}} + \frac{342.75}{Re^{1.5}}\right)^{-1.0}$$
If $K_v < 1.0$, re-calculate $A = A_{unviscous} / K_v$ iteratively until convergence.
2. Governing Equations & Mathematical Formulation
$$A = \frac{11.78 \cdot Q_{m^3/h}}{K_d K_w K_v K_c} \sqrt{\frac{SG}{\Delta P_{kPa}}} \quad [A: \text{mm}^2]$$
$$A = \frac{Q_{gpm}}{38 \cdot K_d K_w K_v K_c} \sqrt{\frac{SG}{\Delta P_{psi}}} \quad [A: \text{in}^2]$$
$$K_v = \left(0.9935 + \frac{2.878}{\sqrt{Re}} + \frac{342.75}{Re^{1.5}}\right)^{-1.0} \le 1.0$$
• Liquid is subcooled or non-flashing throughout nozzle acceleration (no vapor bubble inception at throat).
• Fully developed turbulent nozzle flow unless Reynolds number dictates $K_v < 1.0$.
• ASME Code allows certified capacity sizing at 10% overpressure; non-certified thermal relief valves open at up to 25% overpressure.
• Omitting viscosity correction for heavy crude, vacuum residues, or heavy lube oils ($> 50\text{ cSt}$), resulting in severe undersizing.
• Assuming liquid relief has the same $K_d$ as gas relief ($K_{d,liq} = 0.65$ vs $K_{d,gas} = 0.975$).
• Ignoring pressure recovery behind the seat which can cause conventional liquid valves to cycle rapidly (flutter) when overpressure is under 10%.
3. Applied Engineering Worked Example
Fluid: Lube Oil ($SG = 0.88$, dynamic viscosity $\mu = 140\text{ cP}$ at relieving temp)
Required Relieving Flow: $Q = 180\text{ gpm}$ ($40.88\text{ m}^3\text{/h}$)
Set Pressure: $P_{set} = 150\text{ psig}$
Overpressure: $10\% \implies P_1 = 165\text{ psig}$
Backpressure: Atmospheric header ($P_b = 0\text{ psig}$), $\Delta P = 165\text{ psi}$
-
Preliminary Uncorrected Area ($K_v = 1.0$):
$$A_{prelim} = \frac{180}{38 \times 0.65 \times 1.0 \times 1.0 \times 1.0} \sqrt{\frac{0.88}{165}} = \frac{180}{24.7} \times 0.07303 = 0.5322\text{ in}^2$$ -
Calculate Orifice Reynolds Number:
$$Re = \frac{Q \cdot (2800 \cdot SG)}{\mu \sqrt{A}} = \frac{180 \times (2800 \times 0.88)}{140 \times \sqrt{0.5322}} = \frac{443,520}{140 \times 0.7295} = 4,342$$ -
Calculate Viscosity Correction Factor $K_v$:
$$\sqrt{Re} = \sqrt{4,342} = 65.894, \quad Re^{1.5} = 286,112$$
$$K_v = \left(0.9935 + \frac{2.878}{65.894} + \frac{342.75}{286,112}\right)^{-1} = (0.9935 + 0.04368 + 0.00120)^{-1} = (1.03838)^{-1} = 0.963$$ -
Corrected Required Area:
$$A_{req} = \frac{A_{prelim}}{K_v} = \frac{0.5322}{0.963} = 0.5526\text{ in}^2$$ -
Select API 526 Orifice:
- G Orifice area $= 0.503\text{ in}^2 < 0.5526\text{ in}^2$ (Insufficient)
- H Orifice area $= 0.785\text{ in}^2 > 0.5526\text{ in}^2$ (Selected)
Selected: 2H3 Valve with H Orifice ($A = 0.785\text{ in}^2$).
Interactive Practice Drill: Liquid Relief Sizing & Viscosity Correction Factors (Kv)
Completed this lesson?
Record your study progress, build your daily streak, and unlock +25 XP toward your next engineering tier.
Connected ChemProCal Tool
Advanced hydraulic flow calculator for liquid phase.