Worked Example: Flare Stack Thermal Radiation, Flame Tilt & Sterile Exclusion Zone Sizing (API 521 & Brzustowski Plume Method)

Step-by-step engineering sizing of an emergency flare stack for a 120 MMSCFD gas terminal blowdown. Calculates heat release, emissive fraction, Brzustowski flame tilt, required stack height, and grade radiation exclusion radii under 9 m/s wind.

Published
October 21, 2026
Reading Time
~9 Minutes
Technical Review
Process Design Engineer (B.Tech Chemical Engineering, 5+ Yrs Experience)
📑 Table of Contents (Tap to view sections)

    1. Problem Statement & Facility Architecture

    An onshore natural gas processing terminal must design an elevated emergency blowdown flare stack. The flare system must safely dispose of the maximum credible emergency relief load: an instantaneous total platform depressurization initiated by a fire detection interlock.

                      Flame Center (xc, H + yc)
                            ( * )  <- Flame deflected by wind uw
                           /  |  \
                          /   |   \
                         /    |    \  Thermal Radiation K (kW/m²)
                        /     |     \
                       /      |      \
                      /       |       \
    =================[ Tip ]==+========\========================== Grade Level
                       |               |
                       |               |
                 Stack | H             |
                       |               |
                       |               |
                   [ Base ]======[ R_sterile ]======[ Boundary Fence ]
    

    Relieving Stream & Environmental Parameters

    • Relief Gas Flow Rate ($Q$): $120.0\text{ MMSCFD}$ ($38.54\text{ kg/s} = 138,750\text{ kg/h}$)
    • Gas Composition: Rich natural gas ($90.0\%\text{ CH}_4$, $6.0\%\text{ C}_2\text{H}_6$, $3.0\%\text{ C}_3\text{H}_8$, $1.0\%\text{ N}_2$)
    • Gas Molecular Weight ($M_w$): $17.65\text{ kg/kmol}$
    • Gas Lower Heating Value ($\text{LHV}$): $48.20\text{ MJ/kg}$ ($20,720\text{ Btu/lb}$)
    • Relief Temperature at Flare Tip ($T_{\text{tip}}$): $45.0\text{ }^\circ\text{C}$ ($318.15\text{ K}$)
    • Flare Tip Diameter ($D_{\text{tip}}$): $0.6096\text{ m}$ ($24.0\text{ inches}$)
    • Design Crosswind Velocity ($u_w$): $9.0\text{ m/s}$ ($32.4\text{ km/h} \approx 20.1\text{ mph}$)
    • Relative Humidity ($\text{RH}$): $60\%$ at $25\text{ }^\circ\text{C}$ ambient
    • Solar Radiation Flux ($K_{\text{solar}}$): $0.79\text{ kW/m}^2$ ($250\text{ Btu/hr}\cdot\text{ft}^2$)

    Engineering Permissible Radiation Thresholds (API 521 Table 10)

    Zone / Exposure Condition Maximum Allowable Incident Radiation ($K_{\text{total}}$) Personnel / Structural Exposure Condition
    Zone 1: Flare Base & Stack Access $9.46\text{ kW/m}^2$ ($3000\text{ Btu/hr}\cdot\text{ft}^2$) Short escape only (max 30 seconds with appropriate clothing)
    Zone 2: Process Area & Operators $4.73\text{ kW/m}^2$ ($1500\text{ Btu/hr}\cdot\text{ft}^2$) Action required within 2 to 3 minutes; escape path
    Zone 3: Property Boundary / Fence $1.58\text{ kW/m}^2$ ($500\text{ Btu/hr}\cdot\text{ft}^2$) Continuous personnel occupancy; no protective clothing

    Sizing Objectives

    1. Calculate the total heat release ($Q_h$) and radiant emissive fraction ($F$).
    2. Compute the flare tip exit velocity and Mach number ($M$).
    3. Determine the flame length ($L_f$) and flame center deflection coordinates $(x_c, y_c)$ using the Brzustowski-Sommer plume model.
    4. Calculate the minimum stack height ($H_{\text{stack}}$) required to keep radiation at the process area boundary ($50\text{ m}$ from base) below $4.73\text{ kW/m}^2$.
    5. Determine the ground-level sterile exclusion zone radius ($R_{\text{sterile}}$) for continuous boundary exposure ($1.58\text{ kW/m}^2$).

    2. Governing Equations & Methodology

    2.1 Total Heat Release Rate ($Q_h$)

    The heat release rate of the flare represents the total thermodynamic energy rate discharged to the atmosphere:

    where $\dot{m}$ is mass flow rate ($\text{kg/s}$) and $\text{LHV}$ is in $\text{kJ/kg}$ or $\text{kW}/(\text{kg/s})$.

    2.2 Radiant Fraction ($F$)

    Per API Standard 521 Section 5.7.2.3, the fraction of liberated heat radiated to the surrounding environment depends on the molecular weight, burner velocity, and soot-producing tendencies of the gas:

    For $M_w = 17.65\text{ kg/kmol}$:

    2.3 Flame Length ($L_f$) - API 521 / Brzustowski Correlation

    The flame length represents the continuous combustion envelope from the tip to the plume burnout point:

    2.4 Wind Deflection & Flame Center Coordinates

    Under a crosswind $u_w$, the flame bends in the downwind direction. Brzustowski and Sommer define the dimensionless velocity momentum ratio:

    The coordinates of the flame center relative to the flare tip are:

    where the flame tilt angle $\theta$ relative to the vertical axis is given by:

    2.5 API 521 Simple Point Source Radiation Equation

    At any grade observation point located at distance $R$ from the flame center $(x_c, H + y_c)$:

    where: * $K$ = Incident thermal radiation at the receiver ($\text{kW/m}^2$) * $\tau$ = Atmospheric transmissivity factor ($0.85\text{--}0.95$ depending on humidity and distance) * $R$ = True 3D straight-line distance from the flame center to the receiver ($1.8\text{ m}$ above grade):


    3. Step-by-Step Engineering Calculations

    Step 1: Heat Release & Gas Tip Exit Velocity

    Mass Flow Rate:

    Total Heat Release ($Q_h$):

    In imperial units:

    Volumetric Flow Rate at Tip Conditions ($1.013\text{ bar abs}, 45\text{ }^\circ\text{C}$):

    Using real gas density ($\rho_{\text{tip}} = \frac{P M_w}{Z R T}$):

    Tip Area ($D_{\text{tip}} = 0.6096\text{ m} = 24\text{''}$):

    Tip Exit Velocity ($v_{\text{tip}}$):

    Sonic Velocity and Mach Number:

    For natural gas ($\gamma \approx 1.28$, $M_w = 17.65$):

    API 521 Check: Mach number is $0.445 \le 0.50$. The flare tip operates within the recommended subsonic velocity envelope, avoiding extreme acoustic vibration and flame lift-off instability.


    Step 2: Flame Length & Center Coordinates

    Flame Length ($L_f$):

    The burning flame envelope extends $67.0\text{ meters}$ into the air!

    Flame Center Displacement under $9.0\text{ m/s}$ Crosswind:

    Using the Brzustowski momentum ratio:

    The flame center coordinates relative to the tip are:


    Step 3: Determining Required Flare Stack Height ($H_{\text{stack}}$)

    To protect personnel in the process unit ($50\text{ m}$ downwind from stack base, receiver height $1.8\text{ m}$), the total radiation must satisfy:

    Subtracting solar radiation:

    Required Distance from Flame Center ($R_{\text{req}}$):

    Using average atmospheric transmissivity $\tau \approx 0.88$:

    Solving for Stack Height $H_{\text{stack}}$:

    At the process boundary point ($x = 50.0\text{ m}$, $y = 0\text{ m}$ downwind):

    Adding a standard $10\%$ engineering safety margin for wind gust turbulence:


    Step 4: Ground Radiation Profile & Sterile Exclusion Zone Sizing

    With the stack height fixed at $H_{\text{stack}} = 60.0\text{ m}$, the flame center elevation above grade is:

    Effective vertical distance to person ($h = 1.8\text{ m}$):

    Sizing the Sterile Exclusion Zone ($K_{\text{total}} = 1.58\text{ kW/m}^2$ at Boundary Fence):

    Allowable flame radiation:

    Required distance from flame center:

    Now solving for the downwind ground radius ($x_{\text{fence}}$):


    4. Summary of Thermal Radiation Contours

    The complete radial profile from the flare stack base downwind is summarized below:

    Ground Distance from Stack Base ($x$) Distance to Flame Center ($R$) Flame Radiation ($K_{\text{flame}}$) Solar Flux ($K_{\text{solar}}$) Total Incident Radiation ($K_{\text{total}}$) Permissible Occupancy / API Status
    $0.0\text{ m}$ (Stack Base) $83.9\text{ m}$ $3.72\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $4.51\text{ kW/m}^2$ Permissible for short maintenance (< 3 min)
    $18.8\text{ m}$ (Directly Under Flame) $81.8\text{ m}$ $3.92\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $4.71\text{ kW/m}^2$ Peak grade radiation point
    $50.0\text{ m}$ (Process Boundary) $87.5\text{ m}$ $3.43\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $4.22\text{ kW/m}^2$ COMPLIANT ($\le 4.73\text{ kW/m}^2$)
    $100.0\text{ m}$ $115.3\text{ m}$ $1.97\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $2.76\text{ kW/m}^2$ Restricted access area
    $150.0\text{ m}$ $154.9\text{ m}$ $1.09\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $1.88\text{ kW/m}^2$ Transition zone
    $182.0\text{ m}$ (Sterile Fence) $182.2\text{ m}$ $0.79\text{ kW/m}^2$ $0.79\text{ kW/m}^2$ $\mathbf{1.58\text{ kW/m}^2}$ STERILE BOUNDARY (Continuous public/worker access)

    5. Engineering Observations & Best Practices

    1. Wind Dominance on Sterile Zone: A crosswind of $9.0\text{ m/s}$ shifts the flame center downwind by nearly $19\text{ m}$, elongating the downwind exclusion perimeter from $163\text{ m}$ (calm) to $182\text{ m}$. In plant layouts, the flare must be positioned downwind of prevailing seasonal wind directions relative to offices and control rooms.
    2. Tip Mach Number Safety: Sizing the tip at $24\text{ inches}$ ($610\text{ mm}$) yields a Mach number of $0.445$. While API 521 allows Mach numbers up to $0.50$ for emergency peak flaring, higher velocities cause severe acoustic resonance ($> 115\text{ dBA}$) and risk lifting the flame off the burner rim.
    3. Smoke Suppression: Rich hydrocarbon gas ($M_w = 17.65$) burns with moderate soot formation. For smokeless capacity up to $20\%$ of peak relief, high-pressure steam injection ($0.3\text{ kg steam/kg gas}$) or an air-assisted blower shroud should be integrated.
    
    Apply This Fundamental

    Flare Stack Thermal Radiation & Dispersion Safety Screener

    Apply this methodology directly in the ChemProCal calculator.

    Open Calculator →

    References

    • API Standard 521: Pressure-relieving and Depressuring Systems (7th Edition, American Petroleum Institute, 2020) - Standard [Link ↗]
    • ISO 23251: Petroleum, petrochemical and natural gas industries - Pressure-relieving and depressuring systems (2nd Edition, International Organization for Standa) - Standard [Link ↗]
    • GPSA Engineering Data Book, Section 5: Relief Systems and Flares (14th Edition, Gas Processors Suppliers Association) - Standard [Link ↗]
    • Brzustowski, T.A. and Sommer, E.C. - Predicting Radiant Heating from Flares (API Proceedings, Division of Refining, 1973) - Paper
    🛠️ Tool Integration

    Apply Methodology in Flare Stack Thermal Radiation & Dispersion Safety Screener

    Execute complete engineering simulations using the governing mathematical equations from this guide:

    Apply the exact mathematical principles from this fundamental directly inside the official Flare Stack Thermal Radiation & Dispersion Safety Screener engine.

    Engineering Standards & Peer-Review Governance

    Authored & Verified by Process Design Engineer (B.Tech Chemical Engineering, 5+ Yrs Experience)

    Formulations adhere strictly to API Standard 521 / ISO 23251 thermal radiation models and the Brzustowski-Sommer plume trajectory method. Atmospheric transmissivity and radiation thresholds verified against GPSA Section 5 design guidelines.

    Domain Equipment design
    Governing Standards API Standard 521 (7th Edition, 2020), ISO 23251, GPSA Engineering Data Book Section 5
    Content Classification Worked Example
    Verification ✓ Verified against API 521 & GPSA Thermal Radiation Design Guidelines