1. Calculation Scope & Governing Equations
This module calculates equilibrium vapor pressure, liquid density, and commercial compliance for Liquefied Petroleum Gas (LPG) blends (propane/butane) per GPA Standard 2145 / ASTM D1267.
2. Commercial LPG Specifications (GPA / HD-5)
| LPG Product Grade | Nominal Composition | Max Vapor Pressure @ 37.8°C (100°F) |
|---|---|---|
| Commercial Propane (HD-5) | ≥ 90% Propane, ≤ 5% Propylene, ≤ 2.5% Butanes | ≤ 1,434 kPa (208 psig) |
| Commercial Butane | ≥ 95% Butanes (n-butane + isobutane) | ≤ 483 kPa (70 psig) |
| Commercial LPG (70/30 Blend) | 70% Propane / 30% Butane (Winter domestic fuel) | ≈ 1,050 kPa (152 psig) |
3. Engineering Assumptions & Boundary Limits
- Temperature Rating: LPG storage vessels must be designed for maximum summer ambient solar heating (typically 45°C to 50°C design pressure).
- Overfill Protection: Vessels must not exceed 85% liquid volumetric filling at reference temperature to prevent hydrostatic overpressure from thermal liquid expansion.