1. Calculation Scope & Governing Equations
This tool evaluates moist air psychrometrics, dehumidification, and HVAC cooling/heating loads in accordance with the ASHRAE Handbook of Fundamentals.
2. Standard Indoor Comfort & HVAC Design Criteria
| Parameter | ASHRAE Standard 55 Range | Process Control / Cleanroom Limits |
|---|---|---|
| Dry Bulb Temperature | 21.0°C – 25.0°C (70°F – 77°F) | 20.0°C ± 1.0°C (Pharmaceutical manufacturing). |
| Relative Humidity (RH) | 30% – 60% | 45% ± 5% (Data centers / cleanrooms; controls ESD and mold). |
| Maximum Humidity Ratio ($W$) | ≤ 0.012 kg/kg dry air | Prevents condensation on building envelopes and cold ductwork. |
| Enthalpy at Comfort Peak | 45 – 55 kJ/kg dry air | Basis for chiller refrigeration tonnage sizing. |
3. Engineering Assumptions & Boundary Limits
- Atmospheric Pressure: Defaults to sea-level standard (101.325 kPa). High-elevation cities (e.g. Denver, Bogotá) experience elevated humidity ratios for identical wet bulb depressions.
- Sensible Heat Ratio (SHR): $\text{SHR} = Q_{\text{sensible}} / (Q_{\text{sensible}} + Q_{\text{latent}})$; typical air handling units operate at $\text{SHR} = 0.70–0.85$.