📑 Table of Contents (Tap to view sections)
What is the Overall Heat Transfer Coefficient?
The Overall Heat Transfer Coefficient, denoted U, is the single most important number in heat exchanger design. It tells you how effectively heat moves from one fluid to another across the exchanger wall — accounting for every resistance in the path: the hot-side film, the tube wall, fouling deposits, and the cold-side film.
U appears directly in the fundamental heat exchanger design equation:
$$Q = U \cdot A \cdot \Delta T_{lm}$$where \(Q\) is the heat duty (W), \(A\) is the heat transfer area (m²), and \(\Delta T_{lm}\) is the Log Mean Temperature Difference. A higher U means you need less area for the same duty — directly reducing equipment size and cost.
U is not a fixed material property — it depends on your fluid velocities, fluid properties, fouling condition, and geometry. It must be calculated for each service, not assumed from generic tables.
The Thermal Resistance Analogy
The best way to understand U is through electrical resistance analogy. Just as resistors in series add up to reduce current, thermal resistances in series add up to impede heat flow.
For a plain tube wall with fluid on both sides, five resistances act in series:
- Hot-side film resistance — boundary layer on the process side: \(R_{hot} = 1/h_i\)
- Hot-side fouling resistance — scale, deposits, biofilm: \(R_{fi}\)
- Wall conduction resistance — tube wall material: \(R_w = t_w / k_w\)
- Cold-side fouling resistance — cooling medium deposits: \(R_{fo}\)
- Cold-side film resistance — coolant boundary layer: \(R_{cold} = 1/h_o\)
These resistances add directly to give the total resistance, and U is its reciprocal:
$$\frac{1}{U} = \frac{1}{h_i} + R_{fi} + R_w + R_{fo} + \frac{1}{h_o}$$The U-Value Equation
For a flat plate or thin-walled tube (where area correction is negligible), the equation simplifies to:
$$U_{clean} = \frac{1}{\dfrac{1}{h_i} + \dfrac{1}{h_o} + R_w}$$ $$U_{fouled} = \frac{1}{\dfrac{1}{h_i} + R_{fi} + \dfrac{1}{h_o} + R_{fo} + R_w}$$For a thick-walled tube where the inner and outer areas differ significantly, a more rigorous form corrects for geometry using inner and outer radii — this is handled by the full Heat Exchanger Rating tool.
Wall Thermal Resistance
For a tube wall, the wall resistance is:
$$R_w = \frac{t_w}{k_w}$$where \(t_w\) is wall thickness (m) and \(k_w\) is the tube material thermal conductivity (W/m·K). Typical values:
| Material | k (W/m·K) | R_w (m²·K/W) for 2 mm wall |
|---|---|---|
| Carbon Steel | 50 | 0.00004 |
| 316L Stainless Steel | 16 | 0.000125 |
| Admiralty Brass | 111 | 0.000018 |
| Titanium Grade 2 | 21 | 0.000095 |
For metals, \(R_w\) is typically the smallest resistance — often less than 5% of the total. The dominant resistance is almost always one of the film coefficients.
Film Heat Transfer Coefficients — What Controls U?
The film coefficient \(h\) depends on fluid properties and flow conditions. It is typically estimated from Nusselt number correlations:
$$h = \frac{Nu \cdot k}{D}$$where \(Nu\) is the Nusselt number (from a correlation such as Dittus-Boelter or Gnielinski), \(k\) is fluid thermal conductivity, and \(D\) is the characteristic diameter.
Typical film coefficient ranges by service:
| Service | h (W/m²·K) |
|---|---|
| Natural gas / vapour (low pressure) | 20 – 100 |
| Compressed gas / air (high velocity) | 100 – 500 |
| Light hydrocarbon liquid (turbulent) | 500 – 2,000 |
| Water / cooling water (turbulent) | 3,000 – 10,000 |
| Condensing steam | 5,000 – 20,000 |
| Boiling water (pool boiling, nucleate) | 2,000 – 40,000 |
| Viscous crude oil or heavy liquid | 100 – 500 |
The lowest film coefficient in the pair controls U. If one side is gas and the other is water, the gas side is almost always the bottleneck — regardless of how good the water-side coefficient is.
Fouling Resistance
Fouling is the accumulation of scale, deposits, biofilm, or corrosion products on heat transfer surfaces. It acts as an additional insulating layer and reduces U over time.
TEMA (Tubular Exchanger Manufacturers Association) publishes standard fouling resistance values in Table RGP-T-2.4. Common values:
| Service | R_f (m²·K/W) |
|---|---|
| Cooling tower water (treated) | 0.000176 |
| Sea water (below 52°C) | 0.000088 |
| Light hydrocarbon process streams | 0.000176 |
| Heavy fuel oil or crude | 0.000528 – 0.000881 |
| Steam (non-oil bearing) | 0.000088 |
Fouling is additive — a significant fouling allowance can reduce U by 20–50% compared to the clean value. Always size the exchanger area for the fouled U, and verify that the clean U gives acceptable startup performance.
Typical Overall U-Values by Service
| Service | U (W/m²·K) |
|---|---|
| Water–water (shell and tube) | 800 – 2,000 |
| Hydrocarbon liquid – water | 300 – 700 |
| Gas – gas | 15 – 80 |
| Gas – liquid | 20 – 150 |
| Condensing steam – water | 1,000 – 4,000 |
| Condensing steam – oil | 100 – 400 |
| Reboiler (thermosiphon, HC–steam) | 500 – 1,500 |
| Air cooler (forced draft, liquid side) | 30 – 120 (bare tube) |
Use these ranges for preliminary area estimates only. For detailed design, calculate U from first principles using your actual film coefficients and fouling values.
Worked Example
A crude oil cooler (shell and tube) has the following design basis:
- Shell side: crude oil, \(h_i = 600\) W/m²·K, \(R_{fi} = 0.0004\) m²·K/W
- Tube side: cooling water, \(h_o = 5000\) W/m²·K, \(R_{fo} = 0.000176\) m²·K/W
- Carbon steel tube wall: \(R_w = 0.00004\) m²·K/W
Step 1: Clean U-value
$$\frac{1}{U_{clean}} = \frac{1}{600} + \frac{1}{5000} + 0.00004 = 0.001667 + 0.0002 + 0.00004 = 0.001907$$ $$U_{clean} = 524 \text{ W/m}^2\text{·K}$$Step 2: Fouled U-value
$$\frac{1}{U_{fouled}} = 0.001907 + 0.0004 + 0.000176 = 0.002483$$ $$U_{fouled} = 403 \text{ W/m}^2\text{·K}$$Step 3: Fouling penalty
$$\text{Penalty} = \frac{524 - 403}{524} = 23.1\%$$Step 4: Dominant resistance analysis (clean)
- Crude oil film: \(1/600 = 0.001667\) → 87.4% of total resistance
- Cooling water film: \(1/5000 = 0.0002\) → 10.5%
- Wall: 2.1%
The crude oil film completely controls U. Any improvement in the water-side coefficient is wasted — the engineering focus should be on increasing the shell-side velocity or using twisted-tape inserts to improve \(h_i\).
The side with the lowest film coefficient always controls U. Doubling the controlling film coefficient almost doubles U. Doubling the already-high film coefficient achieves almost nothing.
Common Engineering Mistakes
- Assuming U from tables without calculating it. Table values are ranges — your actual value may be outside the range due to viscosity, velocity, or geometry.
- Sizing on clean U instead of fouled U. Always size the area using \(U_{fouled}\). Check that the exchanger performs acceptably at startup with \(U_{clean}\).
- Ignoring the dominant resistance. Adding area is expensive — improving the controlling film coefficient (by increasing velocity or changing geometry) is usually more cost-effective.
- Using the flat-plate formula for thick-walled tubes. If the tube OD/ID ratio exceeds 1.2, the area-correction form must be used.
- Ignoring laminar flow. If Re < 2300, the film coefficient drops sharply and U can be 5–10× lower than the turbulent estimate.
What Correlation Valid Range Applies?
- The Dittus-Boelter correlation for \(h\): valid for Re > 10,000, 0.7 < Pr < 160, L/D > 10.
- The Gnielinski correlation: more accurate for 3,000 < Re < 5,000,000.
- For laminar flow (Re < 2300): use the Sieder-Tate or constant Nu (Graetz problem).
- Shell-side: use the Bell-Delaware method for segmental baffles — available in the full Heat Exchanger Rating tool.
When to Use the Full ChemProCal Tool
The estimator above gives you U from known film coefficients and fouling values. When you need to:
- Calculate shell-side and tube-side film coefficients from first principles (fluid properties, velocity, geometry)
- Run a complete exchanger rating with LMTD, F-factor, required area, pressure drops
- Apply the Bell-Delaware method for shell-side rating
- Evaluate multiple tube passes and baffle configurations
→ Use the Heat Exchanger Rating full tool.
Related Articles
Heat Exchanger Rating
Apply this methodology directly in the ChemProCal calculator.
Open Calculator →Live Overall Heat Transfer Coefficient (U-Value) Estimator
Adjust parameters below to test the methodology equations in real time before running full simulations: