Multi-Input Multi-Output (MIMO) Systems & Relative Gain Array (RGA)
Covers Multi-Input Multi-Output (MIMO) interaction analysis via Bristol's Relative Gain Array (RGA), detailing matrix formulation, diagonal and off-diagonal pairing rules, interaction metrics, and distillation dual-composition control.
1. Theoretical Foundations & Engineering Mechanics
Loop Interaction in Multivariable Processes
When multiple Single-Input Single-Output (SISO) feedback loops operate simultaneously on a process unit (e.g., controlling both distillate purity $x_D$ and bottoms purity $x_B$ in a distillation column), opening or closing one loop directly alters the dynamic behavior and effective gain of the other loop.
This cross-coupling is analyzed quantitatively using Bristol's Relative Gain Array (RGA), denoted as $\mathbf{\Lambda}$.
Definition of Relative Gain ($\lambda_{ij}$)
For a multivariable process relating outputs $\mathbf{y}$ to inputs $\mathbf{u}$, the relative gain $\lambda_{ij}$ between controlled variable $y_i$ and manipulated variable $u_j$ is defined as the ratio of two open-loop gains:
$$\lambda_{ij} = \frac{\left.\frac{\partial y_i}{\partial u_j}\right|_{\text{all other } u_k = 0}}{\left.\frac{\partial y_i}{\partial u_j}\right|_{\text{all other } y_k = 0}} = \frac{\text{Gain with all other loops OPEN}}{\text{Gain with all other loops CLOSED under perfect control}}$$
Algebraic Matrix Computation
For a steady-state gain matrix $\mathbf{K}$, the RGA matrix is computed directly via Hadamard (element-by-element) product:
$$\mathbf{\Lambda} = \mathbf{K} \otimes (\mathbf{K}^{-1})^T$$
For a standard $2 \times 2$ system with gain matrix $\mathbf{K} = \begin{bmatrix} K_{11} & K_{12} \\ K_{21} & K_{22} \end{bmatrix}$:
$$\lambda_{11} = \frac{1}{1 - \frac{K_{12} K_{21}}{K_{11} K_{22}}} = \frac{K_{11} K_{22}}{\det(\mathbf{K})}$$
$$\mathbf{\Lambda} = \begin{bmatrix} \lambda_{11} & 1 - \lambda_{11} \\ 1 - \lambda_{11} & \lambda_{11} \end{bmatrix}$$
Canonical Mathematical Properties of RGA
- Sum of Rows and Columns: Every row and every column of $\mathbf{\Lambda}$ sums identically to exactly $1.0$:
$$\sum_{j=1}^n \lambda_{ij} = 1.0, \quad \sum_{i=1}^n \lambda_{ij} = 1.0$$ - Scale Invariance: Multiplying any row or column of $\mathbf{K}$ by an arbitrary scaling factor (e.g., unit conversions) leaves $\mathbf{\Lambda}$ completely unchanged.
Industrial Loop Pairing Rules
- $\lambda_{ij} = 1.0$: Perfect decoupling. Closing other loops has zero effect on loop $(i-j)$. Pair $u_j$ with $y_i$.
- $0.5 < \lambda_{ij} < 1.0$: Moderate interaction. Pair $u_j$ with $y_i$ along diagonal.
- $\lambda_{ij} > 1.0$: Interactions act in opposition to open-loop effect; closing other loops decreases effective gain.
- $\lambda_{ij} = 0.5$: Maximum interaction; loops cannot be decoupled independently.
- $\lambda_{ij} < 0$ (CRITICAL SAFETY RULE): NEVER pair on negative relative gains! A negative $\lambda_{ij}$ means the effective process gain reverses sign when the companion loop is closed or goes into manual/saturation, causing the feedback loop to instantly become unstable.
2. Governing Equations & Mathematical Formulation
$$\mathbf{\Lambda} = \mathbf{K} \otimes (\mathbf{K}^{-1})^T$$
$$\lambda_{11} = \frac{1}{1 - \frac{K_{12} K_{21}}{K_{11} K_{22}}}$$
$$\sum_{j=1}^n \lambda_{ij} = 1.0, \quad \sum_{i=1}^n \lambda_{ij} = 1.0$$
$$\text{Condition Number: } \gamma(\mathbf{K}) = \frac{\sigma_{max}}{\sigma_{min}}$$
• Gain matrix is evaluated at nominal column steady-state operating point.
• Both controllers are tuned with integral action.
• Distillate receiver drum level and column base sump level are independently controlled.
• Column pressure is held constant.
• Incorrect determinant sign.
• Forgetting the transpose in Hadamard product.
• Recommending negative relative gain pairings.
• Assuming RGA applies to non-square systems without pseudo-inverse.
3. Applied Engineering Worked Example
Standard industrial operating and sizing conditions.
Step-by-Step Analytical Solution:
-
Determinant calculation:
$$\det(\mathbf{K}) = (12.8)(-19.4) - (-18.9)(6.6) = -248.32 - (-124.74) = -248.32 + 124.74 = \mathbf{-123.58}$$ -
Matrix inversion:
$$\mathbf{K}^{-1} = \frac{1}{-123.58} \begin{bmatrix} -19.4 & 18.9 \\ -6.6 & 12.8 \end{bmatrix} = \begin{bmatrix} 0.1570 & -0.1529 \\ 0.0534 & -0.1036 \end{bmatrix}$$
Transposing $(\mathbf{K}^{-1})^T$:
$$(\mathbf{K}^{-1})^T = \begin{bmatrix} 0.1570 & 0.0534 \\ -0.1529 & -0.1036 \end{bmatrix}$$ -
RGA evaluation via Hadamard product:
$$\lambda_{11} = K_{11} \times [(\mathbf{K}^{-1})^T]_{11} = (12.8)(0.1570) = \mathbf{2.009} \approx \mathbf{2.01}$$
Alternatively, using the $2 \times 2$ formula:
$$\lambda_{11} = \frac{K_{11} K_{22}}{\det(\mathbf{K})} = \frac{(12.8)(-19.4)}{-123.58} = \frac{-248.32}{-123.58} = \mathbf{2.009}$$
Using row and column sum properties:
$$\lambda_{12} = 1 - \lambda_{11} = 1 - 2.009 = \mathbf{-1.009}$$
$$\lambda_{21} = 1 - \lambda_{11} = 1 - 2.009 = \mathbf{-1.009}$$
$$\lambda_{22} = \lambda_{11} = \mathbf{2.009}$$
$$\mathbf{\Lambda} = \begin{bmatrix} 2.01 & -1.01 \\ -1.01 & 2.01 \end{bmatrix}$$ -
Loop pairing selection:
- The off-diagonal pairings $(x_D \leftrightarrow S)$ and $(x_B \leftrightarrow R)$ have negative relative gains ($\lambda = -1.01$). Pairing on these channels would destabilize the column if the other loop went into manual or saturated!
- The diagonal pairings have positive relative gains $\lambda = +2.01$.
Definitive Recommendation:
- Pair Distillate purity $x_D$ with Reflux rate $R$ ($u_1 \leftrightarrow y_1$).
- Pair Bottoms purity $x_B$ with Reboiler steam $S$ ($u_2 \leftrightarrow y_2$).